Temperature, inclination and current sensor node
For power line monitoring, with wireless transmission
Applications
- Determination of the electrical current-carrying capacity (ampacity) of high-voltage conductors
- Determination of an current-carrying capacity value (ampacity) over a period of up to 10 days
- Ice loading detection
Special Features
- High-precision sensor system for various physical measurands: Temperature, inclination, current, torsion
- Private LoRa<sup>®</sup> communication network (autonomous and secure)
Description
Power line monitoring is a proven monitoring system for high and extra-high voltages. By reliably capturing measured data, the line potential can be optimised, faults located more quickly and maintenance carried out more efficiently. In the process, several unique selling points of power line monitoring deliver economic advantages.
The model TIC-1-W sensor node monitors the transmission lines directly on the conductor. For this purpose, the energy-autonomous model TIC-1-W sensor nodes are installed directly on the conductor in the spans to determine the various measured values locally and integrally (inclination).
The system is highly efficient and suitable for the following application areas:
- Forecasting of current-carrying capacity (ampacity forecasting)
- Increase of current-carrying capacity (ampacity)
- Hazard identification (conductor breaks)
- Ice loading detection
Basis of power line monitoring
The autonomous model TIC-1-W sensor nodes form the basis of the monitoring system. They generate the energy required for operation directly from the live conductor. The system is supplied by the electrostatic fringe field of the high-voltage conductor (capacitive harvesting). As soon as the required mains voltage is present, the sensor nodes automatically enter the operating state and simultaneously establish wireless communication with the base station.
Thanks to the modularity of the system, the collected measured data can be transmitted in many different ways. Aggregated data (e.g. traffic light values) can be made available directly to the control system for plant operation via IEC protocols (60870-5-101/104).
Power line monitoring provides a comprehensive technical basis for spatially resolved monitoring through the decentralised determination of real, physical measured values.